58 Brocade MLX Series and NetIron XMR Hardware Installation Guide
53-1003267-02
Installing a Brocade MLX-8 router
2
To ensure adequate bonding when attaching the ground lug, a minimum of 20 PSI of torque is
required to be applied to the mounting hardware used to attach the ground lug.
FIGURE 42 Crimping the power supply wire in the lug
4. Connect the -48V cable to the negative terminal and the 0V cable to the positive terminal.
DC return must be isolated from the router ground (DC-I) when connecting to DC power supplies.
5. Replace the transparent cover over the lugs.
Final steps
Complete these steps in the order listed:
• “Attaching a management station”
• “Activating the power source”
• “Verifying proper operation”
Installing a Brocade MLX-8 router
This section describes how to install a Brocade MLX-8 router.
Preparing the installation site
Before installing the router, plan the location and orientation relative to other devices and
equipment. For cooling purposes, allow a minimum of six inches of space between the sides, front,
and the back of the router and walls or other obstructions. If a router is installed in a perforated
enclosure, the perforations must cover at least 60 percent of the surface.
This equipment is suitable for installation in a Network Telecommunication facility and where NEC
requirements apply. Additionally, it may be installed in either a Common Bonding Network (CBN) or
Isolated Bonding Network (IBN). It is not intended for Outside Plant (OSP) installations.
Ensure that the proper cabling is installed at the site.
1 #8 AWG power supply wire